| Parameters | ACTBOXES-40FYL/2880KW/415V | ACTBOXES-40HCYL/3600KW/415V |
| Mining Container Dimensions | 11980 × 2280× 2530 mm | 12192 × 2438× 2896 mm |
| Mining Container Weight | 11.5T (±5%) | 12.5T (±5%) |
| Cooling Tower Container Dimensions | 11980 × 2280× 2530 mm | 12192 × 2438× 2896 mm |
| Cooling Tower Container Weight | 7.2T (±5%) | 8T (±5%) |
| Rack Structure | 21 tiers | 4 Columns × 7 Tiers |
| Miner Capacity | 252 units (12 units × 21 tiers) | 392 units (14 units × 7 storeys × 4 blocks) |
| Compatible Miners | 2U liquid-cooled models | Ant liquid-cooled modelss |
| Load Capacity per Tier | 50 kg | 300 kg |
| Input Voltage | 415V, 3-Phase | 415V, 3-Phase |
| Total Power | 2880 kW (4000A) | 3600 kW (5000A) |
| PDU Configuration | 12 units, each: 2 × C13 + 21 × SA=20, 415V / 60Hz | 12AWG, 20A MCB 1-to-1 Control |
| Single Socket Power | 11520W (16A) | 11520W (16A) |
| Primary Protection | Moulded Case Circuit Breaker (MCCB), LSIG + UVT, 35kAIC | MCCB, LSIG + UVT, 35kAIC |
| Secondary Protection | Moulded Case Circuit Breaker (MCCB), Overload + Short Circuit, 35kAIC | MCB, Overload + Short Circuit, 10kAIC |
| Tertiary Protection | Miniature Circuit Breaker (MCB), Overload + Short Circuit, 10kAIC | AC Fan Ø1070 × 20 Units (4.7kW each) + Aluminum Plate-Fin Heat Exchanger + CDU System |
| Cooling Components | AC Fans Ø910 mm × 20 units (4.7kW each) + Aluminum Plate-Fin Heat Exchanger + CDU System | AC Fans Ø910 mm × 20 units (4.7kW each) + Aluminum Plate-Fin Heat Exchanger + CDU System |
| Main Pipeline | 304 Stainless Steel, DN150 × 3mm | 304 Stainless Steel Pipe DN200 (DN150) × 3mm |
| Water Distributor | 304 Stainless Steel, 60 × 60 × 3mm + 21 outlets | 304 Stainless Steel Pipe 50 × 50 × 2mm + 14 Outlets |
| PLC Control | Siemens, with temperature, pressure, and flow interlock protection | Siemens, with Temperature, Pressure & Flow Interlock Protection |
| Operating Temp | -35°C to 35°C | -35°C to 35°C |